faq

FAQ

Most frequent questions and answers

FAQ

DALI / DALI-2
The power of the dual-color temperature LED strip connected to the SP-2309PRO-5C exceeds the channel limit (e.g., 24V 120W/channel). How can this be resolved?

If the total power of the LED strip does not exceed 480W, there are two possible solutions:

The LED strip (24V) needs to be connected to a 24V power supply.

Solution 1: Cut the LED strip into sections, each with a maximum power of 240W, and connect them separately to the two CCT (dual color temperature) channels of the controller.

Solution 2: Switch the color mode to single-address 7c mode, then solder a power wire to the other end of the LED strip and connect it to the other CCT channel of the controller.

Can the DALI bus be routed together with high-voltage power lines?

Yes, it can. However, if there are too many DALI devices, it’s recommended to separate the DALI bus from high-voltage wiring or to use a shielded 2-core 1.5 mm² cable for better performance.

When adjusting the brightness of a constant current driver, does the current change?

Yes, it does. The labeled current on the fixture is its rated current. During dimming, the driver adjusts the actual current without exceeding the rated value.

Can a dual-color temperature LED driver be connected to a single-color fixture?

Yes, but it must be connected to either the coldest or warmest color channel only.

Why can’t high-voltage input fixtures dim down to 1%?

High-voltage input fixtures will adjust faster when dimming, and below a certain threshold (around 1%), the input voltage and current may become insufficient to light the fixture.

What should be done if the rated current is not labeled on the fixture?

Set the driver to the lowest current setting, measure the input voltage (U) of the fixture, then use the formula: I = P × Efficiency / U

What causes DALI drivers to be unstable or unresponsive online?

Possible causes include:

1. Too many branches in the wiring.
2. Excessive cable length causing voltage to drop below 9V.
3. Interference from third-party DALI devices or control panels.
4. The number of DALI devices on the line exceeds the maximum number of devices that can be connected to the system.
5. Incorrect or duplicate address assignments.
6. Driver not compatible with the control system.
Troubleshooting steps:
1. Connect the driver directly to the DALI master terminal.
2. Use a multimeter to measure the DALI bus voltage at the driver.
3. Disconnect third-party DALI devices or panels and test for the driver’s stability.
4. Disconnect the unnecessary DALI devices first.
5. Use the DALI master to assign the address individually or re-search addresses for each device.
6. Send the DALI master back to us for compatibility testing with our drivers.

Why can SR-2303SAC-HP only switch on/off but not dim?

The user unintentionally set a minimum brightness by holding the “Min.Set” button for three seconds while the brightness was at 100%. To fix this, turn the light on to 100%, then hold the “Min.Set” button for three seconds again to cancel the minimum brightness setting.

Why did the SR-2303SAC-HP get damaged even though the connected TRIAC power supply was under 400W?

1. The power supply’s inrush current at startup was too high, and when multiple fixtures are connected in parallel, it exceeded the MOSFET’s limit, damaging the module.
2. A low power factor (PF) of the power supply distorted the output voltage waveform, causing it to lead or lag beyond the acceptable range for the MOSFET, which led to failure especially under multiple parallel loads.

Can the SR-GW-TDA be used with a gigabit Ethernet switch?

No. Using a gigabit switch causes the gateway to frequently disconnect. However, it works properly with routers that support 100 Mbps auto-negotiation.

Why can’t the SR-2701S-N be discovered using extended or full search on a DALI master?

The device is fine and initialized at the factory. The issue lies with the PC software.

Why does the NFC-powered light fail to turn on and keep flashing?

This phenomenon is not due to a damaged driver it is caused by overcurrent protection. Open the NFC app to check the target current and the maximum current.

After connecting the NFC LED driver to the light, the light turns on and then immediately goes off — what could be the cause?

1. The maximum current is lower than the target current (in the new firmware, the maximum current is fixed and cannot be changed).
2. The LED driver has open-circuit protection: when the lamp voltage exceeds the LED driver’s output voltage by 4.5V, open-circuit protection is triggered, causing the light to turn on and then go off.

What does it mean when ‘AU’ is displayed on the digital display?

This is not a fault. When multiple addresses are set on one controller and the addresses are non-sequential, such behavior may occur. Set the addresses in sequential order to resolve the issue.

Why does DALI Master stop searching for devices before completion, and no devices appear on the left device list?

If the search process stops midway and no devices are listed in the software, it is likely due to an outdated master controller firmware that is incompatible with the PC software.

No matter how the parameters are adjusted on the SR-GW-TDA, the lights always turn off and the minimum brightness cannot be set. What is the reason?

You need to set the Hardware Error High-End Ratio (‰), Hardware Error Threshold Output Percentage (High/Low), and Hardware Error Low-End Ratio (‰) to their maximum values. If not set, there will be a flash during the dimming process.

What does it mean when ‘88’ appears on the digital display after using the product for a while?

Possible reasons for malfunction:
1. The product is damaged.
2. Initialization was not completed.

Why do lights not turn on and off consistently?

Brightness inconsistency between lights is due to variations in the minimum brightness of different drivers. Even if the fade time is the same, differing minimum brightness levels will cause visible inconsistencies.

Why do lights flicker when connected to NFC LED driver?

Possible causes for flickering with NFC LED driver:
1. The target current exceeds the lamp’s rated input current.
2. CLO (Constant Lumen Output) is enabled in the NFC app, but the LED driver does not support CLO.
3. Short-circuit or over-temperature protection has been triggered.
4. Initialization issue with the LED driver.

What can be done if induced voltage is present, and the lights cannot be completely turned off ?

1. Connect the positive output terminal to ground.
2. There may be leakage at the LED strip connection — lift and insulate the connection point. 3. If a faint glow appears only when touching the light fixture with a hand or metal object, but disappears when not touched, this is a normal phenomenon caused by induction. Proper insulation will resolve it.
4. If faint glow appears without physical contact, and the light cannot be turned off, possible causes include:
a. Power supply leakage (product defect).
b. Induced voltage: grounding of LED strip or aluminum profile.
c. Live neutral line (220V): check if the neutral wire is disconnected while the live wire remains connected, or if there’s a short circuit in another electrical device.
d. Add an inductor in parallel to the output (if CCT is not used, you can try connecting only the positive terminal).

How many devices can an IoT gateway support when connected to the Tuya platform?

Tuya platform device limit: One household can connect up to 195 devices due to Tuya’s platform restrictions.

Why does only one gateway appear in the Tuya Smart app when three IoT gateways are connected?

Only one gateway shows in the Tuya app because all gateways have the same UUID. Due to Tuya’s UUID mechanism, only one instance appears. The UUID needs to be modified by returning the gateway to the manufacturer.

Why can’t remaining gateways be bound after finding the first one on the same network?

If multiple gateways have duplicate MAC addresses, the following problems may occur: A. Difficulty or failure when adding the gateway. B. All gateways show as online, but none can discover devices. C. Devices from other gateways appear offline and do not come back online automatically.

A 100W constant voltage light strip (50W cold white + 50W warm white) — during CCT adjustment, does it behave like a constant 50W output?

Yes, the 100W constant voltage strip (50W cold white + 50W warm white) operates as a 50W constant-power variation when adjusting CCT.

Why does the SR-2309PRO-5C output only RGBW in R9 mode?

1. First, confirm that the programmed firmware supports RGBAF mode.
2. Confirm that the output is set to 5A mode.

Why does only one gateway appear in the Tuya Smart app when three IoT gateways are connected?

If the LED strip remains faintly lit after power-off: There may be contact between a copper pad and metal housing, forming a ground path. Insulate the point of contact or connect the controller’s input negative terminal to ground.

When both system failure level and power-on level are set to MASK, what happens when the DALI master and LED driver are powered on simultaneously?

Power-on behavior depends on which components are powered:
1. If only the LED driver is powered on: restores the previous state.
2. If only the gateway is powered on: restores the previous state.
3. If both are powered on at the same time: restores the previous state

When system failure level is set to MASK and power-on level to 10%, what happens when the DALI master and LED driver are powered on together?

When both LED driver and gateway power on simultaneously, the brightness follows the Power-On Level, which is 10%.

When the system failure level is set to 10 and the power-on level is MASK, what happens when the DALI master and the LED driver are powered on simultaneously?

1. For Sunricher’s products, when powered on simultaneously, the brightness follows the system failure level.
2. For LTECH’s driver, the brightness follows the previous brightness before power-off.

Why do some lights on-site only reach 50% maximum brightness?

The devices were tested before leaving the factory but were not reset to factory settings afterward.

Can the 48V output version of SR-2309PRO-5C be used with magnetic track light fixtures?

Yes, but you must note when ordering: “Program 48V high-frequency firmware.”  The current version does not support 48V by default.

Why does “FF” keep flashing?

Possible causes include unstable input power, output short circuit, or a faulty product.

Why does DALI Master show many English prompts after installation?

Right-click the icon, go to “Properties” → “Compatibility,” and check “Run this program as administrator.”

Why do lights flicker when turning on or off with SR-2309PRO-5C?

Try replacing the power supply with a more stable one.

Why can’t the LED driver or controller dim anymore?

1. The MOSFET may be damaged due to a short circuit or excessive current.
2. The minimum current may be incorrectly set to 100%.

Why does a controller (PWM dimming) make a buzzing sound at medium brightness, but not at low or high brightness?

This is due to frequency interactions between the power supply and the controller or between the controller and the lights.

In a DALI system, what is the transmission distance for different wire gauges?

1.5mm² → 300m

1.0mm² → 200m

0.75mm² → 150m

0.5mm² → 100m

Why does the multimeter reading differ from the current value written to the driver, even though the software shows the correct value?

Please make sure the maximum current has also been written; if it hasn’t, the target current setting will not take effect.

Can a 48V DALI constant voltage LED driver be used with a DALI magnetic track module?

No, the lights will continuously flicker.

Why can’t the DALI driver be discovered while other brands work fine?

Sunricher DALI drivers follow the DALI-2 standard and support 251, 252, and 253 commands. Please update the software of your DALI master controller.

Can a constant current driver output to a fixture 15 meters away?

Yes.
1. The total power of the fixtures must not exceed the driver’s output capacity.
2. The maximum voltage of the fixtures should be at least 2V below the driver’s maximum output voltage.
3. Ensure voltage deviation of the light source is minimal; within ±1V to ±2V. Example: For a 36V light source with a batch variation of ±2V, and 2V voltage drop from the cable, the driver voltage must be at least 40V (36 + 2 + 2).

Can a constant voltage driver output to a fixture 16 meters away?

Yes, but only if it’s the capacitor version. Without a capacitor version, if the cable between the driver/controller and the light is over 2 meters, the DS waveform may distort, potentially causing overheating or equipment failure.

Why doesn’t the SRP-2305-MT-48CC150-850 current increase when adjusted?

1. Check if the multimeter is faulty.
2. Check if the switching power supply is malfunctioning.

How much current does the SR-2701S-N consume from the DALI bus?

It depends on the load, but starts at 2mA.

Why is there slight flickering at both low and high brightness on a constant voltage driver?

If the cable length exceeds 2 meters, the DSP waveform may distort, and the output cable may be connected to another driver.

Why can’t the color temperature be adjusted after connecting SR-2309PRO-5C to a GVS system?

The mode is not set correctly. The digital display should show “rc”, not “r.c”.

Why do both the digital display and light flicker simultaneously?

The load is too high, triggering overload protection.

Why does DALI Master throw an error upon opening?

DALI Master requires administrator privileges. Right-click the application, go to “Properties” → “Compatibility”, and check “Run this program as an administrator”.

Why can’t the DALI Center detect the gateway?

1. The PC and the gateway are not on the same local area network (LAN);
2. The DALI Center software must be installed on the C drive.

How to reset the group settings on the SR-GW-TDA?

1.First, delete the groups in the app;
2.Then short-press the configuration button 5 times to clear the groups sent by the app.

Why does the power of SR-2305-MT-48CC100-700 / SR-2309-MT-48CCT100-700 increase?

Because the magnetic track driver’s inductor is positioned near the magnet of the magnetic track light, which generates an induced current. This causes an increase in power consumption and may result in light flicker when turned off.

Why can’t the SR-2309PRO-5C be found in the app when connected to the SR-GW-TDA?

Both the gateway and controller must be powered on at the same time. The gateway must send data after powering on; do not power on the gateway before the driver or controller.

Can DALI-2 panels and sensors work without the DALI master?

No. DALI-2 input devices require the DALI master to forward commands. Without the DALI master, commands cannot be transmitted, so DALI-2 devices depend on the DALI master to work.

SR-DARM16-DIN4: Even though the capacitive load power of the LED is halved, zero-cross detection is present, the power is not exceeded, and the wiring is fine, why does channel sticking still occur?

This occurs due to phase difference caused by live wire being connected across different phases. The relay channels will stick unless the module’s LN power supply and the load are on the same phase, which is required for the zero-cross detection to function effectively.

What if the connected DALI master requires only linear dimming effects for a constant voltage LED driver?

Use the version of the firmware that improves low-brightness performance without soft-on/soft-off effects.

Can a CCT driver be used as a DIM driver for emergency use?

Yes, but the negative terminals of the CCT driver must be connected in parallel to avoid damage.

Why can’t some SR-2701S units turn off?

1. The DALI signal to the relay is insufficient;
2. Relay contact sticking (mechanical failure).

Why doesn’t the light turn on when the signal is disconnected, even though the SR-2701S-DT7 is set to 100% system failure brightness?

The SR-2701S-DT7 is powered by the DALI bus. Without a signal, the internal module has no power and cannot execute the system failure brightness setting.

Why can the SR-2701S-N switch lights on/off but not dim them?

The 0-10V dimming curve is not compatible with the standard DALI logarithmic dimming curve used by the SR-2701S-N.

Why is the red indicator light on the SR-2400AMP illuminated?

Possible reasons: 
1. Signal wire short-circuited at the output; 
2. Wires connected incorrectly; 
3. Signal wire insulation is incomplete and may be touching metal structures like a keel, causing grounding issues.

Why is there visible flickering when using a diffuser film, but not without it?

The switching power supply has high ripple. The diffuser film amplifies this flicker, making it visible to the naked eye.

Why does the SR-2400BRC stop working after replacing the driver or controller?

You need to reassign and store the groups and scenes in the SR-2400BRC for the new devices to function properly.

Why does the SR-2309PRO-5C flicker at low brightness?

One 24V power supply is not sufficient to power multiple controllers. Add additional 24V power supplies to share the load.

Why doesn’t brightness change above 60% when using SR-GW-TDA to control third-party drivers?

Because the third-party drivers use a linear dimming curve, while the TDA gateway outputs a logarithmic curve. Switch the driver to a logarithmic curve to fix the issue.

Is the power factor (PF) of a driver constant?

No. The PF is >0.9 at full load, but decreases during dimming or under partial load.

What new features does the SR-GW-TDA gateway support?

Device group assignments remain unchanged after searching. The APP can control lights even when offline. DALI-2 panels are supported. However, sensors are not supported.

What is thermal protection in LED driver?

The driver sets a thermal protection threshold. If the driver’s internal temperature exceeds this threshold (typically Tc), even if the ambient temperature (Ta) is within range, the driver will reduce power output (dimming the lights) for protection.

Why can’t the DALI Center detect the gateway?

Possible reasons: 
1. A gigabit router is being used; 
2. Dual-band Wi-Fi (2.4GHz + 5GHz) is enabled; 
3. The network adapter may need to be disabled for 5 seconds and then re-enabled.

Why do lights connected to the SRP-2309-24-150LCVT turn off after a period of time?

Possible causes:
1. The lights have entered short-circuit or overload protection, possibly due to poor contact, negative wire short, or insulation issues; 
2. LED driver failure.

Why do lights connected to the SRP-2305-24-150LCV turn off after a period of time?

Possible causes: 
1. The lights have entered short-circuit or overload protection, possibly due to poor contact, negative wire short, or insulation issues; 
2. Power supply failure.

Why doesn’t the constant voltage driver flicker at maximum brightness, but flickers at other levels?

Because both LED drivers are connected to the same LED strip, causing signal interference at non-max brightness.

Why is the SR-2305-MT-48CC100-700 out of sync?

Possible reasons:
1. Different master controllers result in different control behaviors.
2. The controlled devices may have inconsistent parameters.

Can a single controller be used with multiple low-power switching power supplies?

No. Variations in output voltage, current, or other parameters can lead to flickering issues.

Why do SRPM series LED drivers damage LEDs?

Hot-plugging (connecting lights while powered on) causes a brief 12V capacitor discharge, which may burn out the LEDs.

What should be done if the DALI master detects duplicate addresses when searching for DALI drivers and cannot display the addresses, but can still control lights with the same address?

1. Use a digital display module to set fixed addresses before system extension.
2. Perform a fresh installation with the DALI master and re-search all driver/controller addresses (initialize the devices).
3. Remove the devices with duplicate addresses, assign fixed addresses individually, then proceed system extension.

Can I search for NFC LED drivers directly from the HDL’s DALI Master?

Yes, you can. Address reassignment is not necessary—just perform addressing.

Can the SR-2108EA be set to Master mode?

Yes, it can be set to Master mode. However, once set to Master, it will not be able to control other decoders that are in adjustable Slave mode.

Why does flickering occur during color mixing with the SR-2108EA?

  1. The wiring is not properly tightened or the lamp has a loose solder connection.
  2. The internal components of the power supply are damaged.

How many channels and pixels does DMX512 support?

512 channels and 170 pixels.

At what distance or number of connected devices should a DMX signal amplifier be added?

After 200 meters or more than 13 devices.

Why do lights connected to the DMX decoder turn off and become unresponsive when the fader is moved too quickly on the DMX console?

The decoder activates load protection. This usually happens when the power supply can’t handle a rapid voltage increase. Replacing the power supply or disabling the load protection can resolve it—but disabling this function will also disable short-circuit protection.

Why does a DMX signal amplifier output cause one line of lights to keep flashing?

It’s likely due to interference caused by a connected ground wire.

Why is the ‘A’ indicator on the DMX decoder constantly flashing?

  1. The decoder is not receiving a DMX signal.
  2. The DMX signal wiring is reversed.
  3. There are multiple DMX signal sources causing a conflict.

Why do constant voltage to constant current fixtures make a buzzing noise during dimming or standby when connected to a DMX decoder?

It’s caused by the operating frequency.

Can a DMX decoder output full load at high frequency?

  1. Plastic housing versions must reduce power output by half.
  2. Metal housing 4-5 channel versions can handle 6A.
  3. Metal housing versions with 12 or more channels can support full load.

Why can one unit pass the high voltage withstand test, but two connected together fail?

The high voltage test measures the maximum voltage the internal insulation of the power supply can withstand. Failure with two connected units may be due to test equipment or insulation limitations.

Does the end of a DMX line always need a terminating resistor?

Yes, the end of every DMX line must have a termination resistor (0.5W, 120Ω), or else signal interference may occur.

How is DMX512 addressing calculated?

1 segment = 1 pixel = 1 IC chip = number of RGB/RGBW channels; 1 universe = 512 addresses (channels)

Can a DMX RF converter with 8 zones be controlled simultaneously by a wall panel?

Yes, it can.

When the SRP-2108-75CCF is connected to a console and channel 6 is activated, why do the lights start flashing rapidly?

In DMX, different DPs (device profiles) control different decoder channels and effects. You need to select the appropriate DP according to your needs.

Why does the SR-2108FBC-4CH revert to address 1 after being powered off and on, even after address settings?

The device is set to force start from address 1 in auto-addressing mode.

Why can’t the new database be imported into ETS6?

ETS6 requires the product to be certified. If usage is necessary, first create a project in ETS5 (or earlier), then import it into ETS6.

What color types does the SR-KN9100DA2-2CH support?

It supports dim, CCT, RGB, and XY color types.

Why can’t the sequence be activated after programming it on the SR-KNX9512FA?

After editing, you need to bind the color cycle to a group address to enable it.

Why doesn’t pressing the button turn the lights on/off after powering on the SR-KNX9512FA?

The device requires a database download before use. Without the database, the data is empty and the button functionality is disabled.

Why can’t the database be downloaded to the SR-KN9100DA2-2CH via ETS?

The gateway has been updated, and the database has also changed. Different versions of the database are not compatible.

After downloading the configuration, the buttons on SR-KNX9512FA can control independently, but ETS commands control channels 1 and 2 together—why?

The group address written via ETS has combined channels 1 and 2. Assign separate group addresses for each channel to control them independently.

 

Which 0/1-10V controller can directly connect to constant voltage tunable white LED strips?

SR-2002

What is the start-up voltage for Suricher’s 0/1-10V device?

0-10V is 0.5V, 1-10V is 0.9V.

Why do other brands’ 0/1-10V power supplies or controllers turn on at a lower brightness, but Sunricher drivers have a noticeably higher turn-on brightness?

Sunricher drivers have turn-on voltages of 0.5V or 0.9V. If the dimmer outputs a higher initial voltage, then due to the linear dimming curve, the perceived brightness will be higher when lights first turn on.

What do -V, -D, and Date mean?

-V refers to 0/1-10V sensors. -D refers to DALI sensors. Date refers to other output models without sensors.

Why is there no L1 output on the SR-2421-TR5-V?

  1. The L and N wires are reversed. 2. There is no 0-10V signal. 3. Device malfunction.

Can the SR-2411-ZG be used together with the SR-2400P?

Yes. If you plan to use multiple SR-2411-ZG devices to control a group, first group the DALI drivers, then connect the SR-2411-ZGs and set the DIP switches accordingly.

Why is there a noticeable stepping effect when using SR-2421-ZG with a DALI driver?

The SR-2421-ZG may be incompatible with certain DALI drivers. The stepping effect results from overlapping dimming curves of Zigbee and DALI.

What are the differences between SR-ZG2835, SR-ZG2835RAC, and SR-ZG2835RACS?

SR-ZG2835: Zigbee wireless dimming rotory knob. SR-ZG2835RAC: Zigbee phase-cut rotory dimmer (600W). SR-ZG2835RAC-S: Zigbee phase-cut rotory dimmer (500W) (Note: The SR-ZG2835RAC (600W) model has been removed from product software.)

How to wire the SR-ZG9100AS-A in single-line (no neutral) installations?

For lights below 12W, use a bypass device (capacitor): SRSL-01, connected in parallel with any light. 2. For lights above 12W, connect directly. 3. Shorting L and N is for metering purposes

Why can’t the SR-2421-ZG adjust color?

  1. DIP switches 8 and 9 must be set according to the desired color mode.
  2. 0/1–10V control only supports brightness adjustment.

Can the SR-2421-ZG control LED drivers from other brands? Will there be a stepping effect or lack of smooth dimming?

  1. The SR-2421-ZG is compatible with other brands of DALI or 0/1-10V LED drivers.
  2. Compatibility needs to be confirmed on a case-by-case basis.

How to change the color type of SR-2421-ZG?

  1. Power must be turned off before debugging.
  2. Perform a power reset.
  3. If a 0-10V device was previously connected, it must be unbound from the system before modifying the DALI color type. The Helvar DALI master chipset only supports XY mode and does not support RGBW or RGBCCT modes.

Do LED drivers have memory functionality?

Yes. As long as the value is set to MASK, the driver will operate in memory mode.

When SR-2421-ZG is connected to a DALI driver, is the fade time based on the 2421-ZG or the DALI driver?

  1. With Sunricher’s Zigbee gateway, the fade time is the sum of the time set in the 2421-ZG and the DALI driver.
  2. With the Tuya gateway, the behavior is the same.

In a Zigbee system, when brightness is adjusted via the app and then using the remote, is the dimming based on the original brightness level? Are the two linked?

Yes, dimming is based on the previous brightness level. Yes, they are linked. In the Sunricher app, you can pair a Sunricher remote, and brightness changes made via the remote will be reflected in the app.

After a Zigbee device is added to the gateway, can the wall panel still control the lights without a router?

Yes, it can.

With SR-2421-ZG + DALI LED driver, why is there a mismatch in on/off behavior?

Because the lighting power is supplied through the L1 terminal controlled by the relay in the SR-2421-ZG. The live wire must be connected to the L terminal, and the parameters need to be configured consistently.

Which Zigbee wall panels are compatible with the SR-GW-ZG gateway?

The SR-ZG9001T4/K4/K8 series can be added to the SR-GW-ZG gateway but can only be bound to a single light. The SR-ZGP2801K4 panels without factory-printed labels can be added to the gateway and customized. Those with printed labels can only be directly linked to the LED driver.

What is the DIP switch procedure for the SR-2421-XX?

First remove the device from the network → set the DIP switches → then rejoin the network.

Can the switch panel type used with SR-ZG9041A-D be changed?

Yes, it can. 1. Leave a note specifying the panel type when placing the order. 2. Modify the panel type in the Azoula Smart app, then power cycle the device to apply changes.

Will the fade time of the SR-2421-ZG stack when used with other LED drivers?

Yes, it will.

How many SR-2411-ZG units can be connected to an existing DALI system at the same time?

Less than 4 units, and they cannot be controlled simultaneously.

The network indicator light on the SR-GW-ZG lights up but turns off after about a minute, and the app keeps trying to reconnect. Why?

The Zigbee gateway’s memory is full. Reset the gateway to erase all data and settings.

Can Zigbee LED drivers adjust color temperature using a push switch?

Currently, Zigbee LED drivers do not support switching color temperature. DALI and RF models have passed testing for this function.

Why does the LED indicator on the SR-ZG2835 (glass version) keep blinking rapidly? It used to work normally.

It returned to normal after replacing the battery. The blinking may have been caused by an accidental press. After blinking for several days, the battery ran out.

How to fix the issue: ‘Failed to connect to gateway. Please check your network and gateway.’?

This happens because the gateway was reflashed with new firmware, and the app still retains the old gateway info. To fix it, tap repeatedly on the blank area in the top right corner of the app to clear stored data.

Can the IP address of the SR-GW-ZG be changed?

  1. Press the center button 10 times to switch to manual IP mode. The gateway IP becomes fixed at 192.168.0.101 with a subnet mask of 255.255.255.0.
  2. Press the center button 15 times to switch back to DHCP (automatic IP) mode.
  3. Performing a reset will not change the IP mode or gateway name.

Why can’t it connect to the Matter platform?

Sunricher Matter devices do not use Wi-Fi. Instead, they use Thread and require a border router (gateway), such as a HomePod.

Why does the Matter platform say ‘No accessory found’?

  1. The Matter device hasn’t been removed from the previous network. 
  2. There’s a connection issue with the border router.

How do you reset a HomePod?

First power it on and wait 10 seconds, then power it off and wait another 10 seconds, then power it back on and hold the button for 10 seconds.

Why can the device be controlled via the Silvair app, but the sensor doesn’t respond?

1.There’s a configuration issue.
2.A ‘-D’ version (sensorless node) was used instead of a sensor.

Why does the Silvair device go offline and become unresponsive after connecting to the app?

Insufficient power to the signal module may cause the Bluetooth module to go offline.

What is the Bluetooth control range of Silvair?

1.In an open environment, the distance between the transmitter and the receiver is >50m;
2.In an open environment, the mesh distance between two devices is >35m.

Can the Silvair sensor be used alongside other active DALI signal devices?

Yes, it can.

Can the Casambi sensor be used alongside other active DALI signal devices?

Yes, it can.

Why can’t CASAMBI control the lights?

1.Poor contact with the DALI signal wires.
2.A mode was selected in the Casambi app, but the address wasn’t changed.
3.Device malfunction.

How to reset CASAMBI device?

1.Delete it directly from the network.
2. Under a different network, tap “Start,” then quickly power off and back on.

Why do colors become unsynchronized when connecting a fourth RF driver / controller?

Check if the master-slave mode has been enabled.

Does the SR-1009NPD master-slave mode require wiring?

Yes, it does.

When the Bluetooth app connects to only one device and syncs successfully, why does syncing fail on another phone using the same account, network name, and password?

When only one device is present on the app, the mesh network has only one node, which can only be discovered and synced by one app instance. To resolve this, close the Homeelife app on the original phone, and keep it open only on the phone you want to sync.

Why does the SR-2421-SB only show single color in the app even when the DIP switches are correctly set?

This means the mode change was successful. Steps: 1. While powered on, set the DIP switch to single color mode. Search and control it via the app, then delete it. 2. Change to the desired mode, and pair it with the app or remote again.

Why the Bluetooth LED driver can be added to the APP, but it cannot be linked to the remote control?

The address needs to be modified. This can be done directly in the app.

How many devices can the SR-SBP2801K4-FOS control?

It can control up to 30 devices.

How many SR-BUS devices can Homeelife connect to? What is the maximum distance between devices?

Up to 100 devices, with a clear-line distance of 10 meters between each.

Quick Contact

* Your data is securely protected for essential communications only. We won’t share your details or send spam emails, Privacy Policy