KNX DALI Gateway

SR-KN9100-DA2-2CH
Product description
  • The KNX DALI Gateway is a DIN rail module for installation in the distribution board on a 35 mm mounting rail. It
  • is a DALI single-master controller to DALI standard IEC 62386 Parts 101ed2 and 103ed1. The gateway is suitable for use with DALI and DALI-2 systems.
  • It supports Device Type 6, Device Type 8 Tc, Device Type 8 XY coordinate, Device Type 8 RGB with DALI interfaces to IEC 62386 and their integration in a KNX building installation.
  • The DALI gateway has 2 channels DALI output. Up to 64 DALI devices can be connected to each DALI output.
  • DT6 and DT8 devices can all be connected to each DALI output in a mixed configuration. The lamps connected to each DALI channels are controlled via KNX using:
  • broadcast
  • 64 individual lamps
  • 16 lighting groups
  • 16 scenes
  • The fault status (lamps or ballasts) of each DALI device or of the lighting group is sent via the KNX bus by a variety of KNX group objects.

The KNX DALI Gateway is a DIN rail module for installation in the distribution board on a 35 mm mounting rail. It is a DALI single-master controller to DALI standard IEC 62386 Parts 101ed2 and 103ed1. The gateway is suitable for use with DALI and DALI-2 systems. It supports Device Type 6, Device Type 8 Tc, Device Type 8 XY coordinate, Device Type 8 RGB with DALI interfaces to IEC 62386 and their integration in a KNX building installation. The DALI gateway has 2 channels DALI output. Up to 64 DALI devices can be connected to each DALI output. DT6 and DT8 devices can all be connected to each DALI output in a mixed configuration.

Supply Gateway supply voltage 100-240VAC, 50/60Hz
Supply Total current draw from mains Maximum 48mA
Supply Total power consumption via mains Maximum 11W
Supply KNX Bus voltage 21-30V DC, via the KNX/EIB bus
Supply KNX current consumption Maximum 10mA
Supply Power consumption via KNX Maximum 210mW
DALI outputs Number of outputs 2
DALI outputs Number of DALI devices Maximum 64 per output
DALI outputs Supported device types DT6. DT8 Tc, DT8 XY coordinate, DT8 RGB
DALI outputs DALI voltage Typical 16VDO
DALI outputs Maximum supply current 2x250mA
Connections KNX KNX connection terminal, 0.8 mm . solic
Connections DALI outputs & mains voltage Screw terminal, 0.5-2.5 mm ,stranded
Connections Mini USB USB-A to Mini USB data cable (USB 2.0)
Operation an display KNX Button and red LED For assigning the physical address
Operation an display KNX Green LED flashing Indicate the application layer running normally
Operation an display DALI red LED on Indicate DALI fault
Operation an display DALI green LED on Indicate DALI bus running normally
Type of protection IP 20, EN 60 529  
Temperature Operation -5°C.+45℃
Temperature Storage -25℃…+55℃
Temperature Transport 25℃..+70℃
Ambient Humidity <93%, except dewing
Design Dimensions 90.1x72x66.4mm
Mounting On 35mm mounting rai To EN60715